Heat Gain Calculator (Instantaneous Estimate)
Explore instantaneous sensible and moisture heat gains from a building envelope, clear-sky windows, leakage and internal sources. Includes hourly solar comparisons.
This tool estimates instantaneous heat gain from entered envelope components, window sunshine, outdoor air and internal sources. It separates temperature-related and moisture-related gains and shows solar changes during the day. Heat gain at one instant is not the same as the peak cooling load: building storage, weather, controls and ventilation can change timing and capacity requirements.
How to use this tool
- Enter outdoor and indoor design conditions, including the outdoor dew point.
- Enter your latitude, the month and the hour (solar time) to evaluate.
- Enter wall and ceiling areas with their R-values and the temperature above the ceiling.
- Enter window areas for each side with their U-factor, SHGC and any interior shading.
- Add the air-leakage rate, occupants and appliance watts, then read the totals and the hourly table.
Formula
Sensible = max(0, conduction + window sun + 1.08·CFM·Δ°F + 230·people + 3.412·W); Latent = max(0, 0.68·CFM·Δgr + 200·people)
CFM = natural ACH × volume ÷ 60; Δgr is the humidity-ratio difference in grains per pound. Sea-level pressure and fixed air heat factors are assumed. Solar irradiance uses a clear-sky beam fit with an assumed horizontal diffuse term of 10% of beam-normal irradiance and 20% ground reflectance. These are model assumptions, not a local weather prediction. Correction rows show any zero floor applied to negative net gains.
Example
At latitude 40° on July 21 at 4 pm solar time, the simplified sun position is about 36° high and nearly west. The model estimates about 752 W/m² on west glass. With 100 sq ft of glass, SHGC 0.5 and no extra interior shading, that is about 11,926 BTU/h of instantaneous solar gain. Stored heat and release timing are not modeled, so this number alone cannot select an air conditioner.
Frequently asked questions
Can there be moisture gain without sensible gain?
Yes. Humid air can add moisture even when its temperature matches indoors. This tool reports that case and floors negative net sensible and moisture values separately at zero; it does not model humidification or a heating credit.
Is solar time the same as clock time?
No. Longitude, time-zone meridian, equation of time and daylight saving all affect the conversion. Enter local solar time. The model suppresses sun below a 1.15° altitude and does not resolve external shadows.
Which values should I enter?
Use whole-assembly imperial R-values, whole-product window U-factor and SHGC, and natural leakage rather than ACH50. Occupant gains are fixed illustrative values; activity and indoor temperature can change them.
Does this satisfy Manual J or building codes?
No. Thermal storage, wall solar absorption, ducts, mechanical ventilation and some envelope components are omitted. Results can be above or below a full calculation. Equipment selection requires appropriate load methods, manufacturer performance and local requirements.