Duct Size Calculator
Compare round and rectangular metal duct sizes for an airflow using a friction or velocity target. See the selected size, velocity and model assumptions.
This calculator compares straight round and rectangular metal ducts at a specified airflow using either a target friction rate or maximum velocity. It rounds the round diameter upward within an illustrative size list and checks rectangular choices against the selected target. Results describe the entered section, not a complete duct network, fan operating point or code-compliant design.
How to use this tool
- Enter the airflow the duct must carry in CFM.
- Choose equal friction or maximum velocity and enter the target.
- Enter the height you have room for if you need a rectangular duct.
- Read the standard round size, its velocity and friction, and the rectangular options.
Formula
d = (0.109136 × Q^1.9 ÷ f)^(1/5.02); d = 12 × √(4Q ÷ (π V)); De = 1.30 (a·b)^0.625 ÷ (a + b)^0.25
Q is CFM, f is inches of water per 100 ft, d is inches and V is ft/min. The friction expression is an empirical turbulent-flow approximation for galvanized metal duct. Huebscher diameter compares equal flow, friction and length; it is not the diameter of an equal-area circle. Rectangular velocity sizing instead requires actual area a·b/144 ≥ Q/V. Widths are tried in 2-inch steps up to 120 inches.
Example
For 1,000 CFM and 0.10 in. w.c. per 100 ft, the friction fit gives about 13.9 inches. A listed 14-inch duct gives approximately 935 ft/min and 0.097 in. w.c. per 100 ft. A 22 × 8 inch rectangle meets that friction target. For a separate velocity example, 400 CFM at a 700 ft/min maximum needs at least 0.5714 sq ft; a 12 × 8 inch rectangle provides 0.6667 sq ft and runs at 600 ft/min.
Frequently asked questions
What friction rate should I use?
Derive it from available fan pressure and total effective length after allowing for coils, filters, grilles and fittings. The default is an example, not a universal residential allowance.
Can I use this for flexible duct?
Use the manufacturer’s pressure-loss data for the installed flex duct, including compression, bends and supports. A metal-duct size is not a sufficient flex-duct sizing rule.
Does a velocity result meet the friction target too?
Only the selected target governs sizing. Inspect the other calculated quantity separately. Acceptable velocity also depends on sound, outlet performance and system design.
What about shallow rectangles?
A large aspect ratio increases surface and may cause practical, acoustic or reinforcement problems. The 4:1 notice is a design prompt, not a compliance limit. Confirm available inside dimensions and fabrication details.
Sources
Last updated: 2026-10-30